The GE Digital Energy SG Series is one of the best performing and most reliable three-phase UPS systems, providing critical power protection for a wide range of applications. Every SG Series system operates in double conversion mode with true on-line VFI (voltage and frequency independent) operation, yielding the maximum levels of power reliability for all mission critical processes. The Digital Energy SG Series was developed using GE’s Design for Six Sigma methodology to ensure that the product fully meets customer requirements and expectations.
Read More

Specifications Features and Benefits Options

Specifications

Topology True on-line, double conversion (VFI) with integral static switch and internal maintenance bypass
Technology Advanced IGBT with SVM strategy, microprocessor controlled at optimal switching frequency
Operating Modes True on-line double conversion, automatic bypass, frequency converter, RPA™ up to eight (8) units
Output Power Rating kVA 400 500
Output Power Factor .8 .9
Output Power Rating (kW) 320 450
Dimensions W x D x H (inches) 81 x 33 x 77 81 x 33 x 77
Weight w/o Batteries (lbs) 4600 5100
Noise Level dB(A) 65
Input Voltage (VAC) 480V, 3 Phase, 4 Wire w/ground (grounded WYE)
Input Voltage Range -20% to +15% (without battery discharge)
Input Frequency 60Hz +/-10%
Input Power Factor .8 PF (.93 with input filter)
Output Voltage (sinusoidal) (VAC) 480V, 3 Phase, 4 Wire w/ground
Output Frequency 60Hz +/-10%
Output THD at Linear Load <2%
Output THD at Non-linear Load <3%
Crest Factor 3:1
Overload Capability on Inverter 125% @ 10 min., 150% @ 1 min.
Overload Capability on Automatic Bypass 200% @ 5 min., 110% continuously
Output Voltage Regulation
   Static +/- 1%
   0-100% Step Load +/- 3%
Fault Clearing Capability
   Inverter - 220% for 100 msec. / 700% for 1.2 msec
   Static Bypass - 100 KAIC
System Efficiency
   100% Load 94.0 93.8
   50% Load 94.2 94.4
Ambient Operating Temp. 32°-104°F (0°- 40°C)
Color RAL 9003 (white)
Classifications and Listing UL 1778 / IP20 / NEMA-PE-1 / ISO9001
RFI and Surge Protection EN 50091-2 / IEC 62040-2 / IEEE 587 B / FCC Class A compliance
Standard Connectivity RS-232; programmable alarm contacts; programmable relays, SNMP (optional)
Warranty Twelve (12) months after commissioning or eighteen (18) months after shipment, whichever occurs first *

* Extended Warranties available

Request a quote

Contact Us: (866)432-1711