Single Phase GE IT Series UPS
IT Series UPS Rack
Single Phase GE IT Series UPS 2
IT Series UPS Tower
« »
GE IT Series UPS

GE's IT Series UPS delivers cost-effective power protection in both tower and 19-inch rack format. Equipped with AVR (Automatic Voltage Regulation), the range is ideal for server, data storage, networking and point of sale applications. The units are equipped with RS232 and USB communication ports as standard, and with an RJ11 port for telephone/modem protection.

The IT Series is a line interactive UPS with AVR (Automatic Voltage Regulation) ensuring a pure sine wave output and preventing damage due to power outages, voltage fluctuations and transient surges. All IT Series UPS have hot-swappable batteries and are provided with a two-year product warranty.

Features & Benefits

• High efficiency at all loads - Ideal for servers supporting varying load levels

• Advanced battery protection - Protection of the UPS core component

• Hot swappable batteries - Battery replacement without removing the load

• Regular automatic battery test - No surprises in the event of utility failure

• Short circuit and overload protection - UPS protection from external errors

• Cold start - UPS can start even without the utility present

• Single Phase Output Voltages -125V

• 50/60 auto-sensing - Can be used as a frequency converter

• 95% efficiency - Low losses and greater energy savings

• Intelligent LED display - Quick visual of UPS, load and battery status

• Wide operating temperature - UPS can operate between 0°C to 40°C

GE IT Series UPS Technical Specifications
MODEL NUMBER UPS0600ITSIT , UPS1000ITSIT , UPS1500ITSIT , UPS2000ITSIT
POWER RATING OUTPUT CAPACITY 600VA / 360W , 1000VA / 600W , 1500VA / 900W , 2000VA / 1200W
POWER FACTOR OUTPUT POWER FACTOR 0.6 pf
INPUT VOLTAGE
FREQUENCY
INPUT POWER CONNECTION
120V +/- 10% at line input, single phase
50 or 60 Hz +/- 5Hz auto-sensing
Detachable 5-15P , Detachable 5-15P , Hardwired 5-15P , Hardwired 5-20P
OUTPUT VOLTAGE (on battery)
VOLTAGE (on mains)
VOLTAGE THD
FREQUENCY (on battery)
VOLTAGE REGULATION (AVR)


OUTPUT RECEPTACLES - POWER DISTRIBUTION
Pure sine wave at +/- 5% of nominal, -10% of nominal after low battery warning
120V, -12%/+10%
< 5% @ 100% resistive load with 80% battery capacity
50 or 60 Hz +/- 5% auto-sensing
AVR automatically increases (boost) output voltage 17% above input voltage if -9% to -25% of nominal. AVR decreases (buck) output voltage 14% below input voltage if +9% to +25% of nominal.

(4) 5-15R , (4) 5-15R , (6) 5-15R , (6) 5-15R
PROTECTION & FILTERING SPIKE PROTECTION
EMI/RF FILTER
OVERLOAD PROTECTION
TRANSFER TIME
SHORT CIRCUIT
780 Joules/6500A
10dB @ 0.15MHz, 50 dB @ 30 MHz
UPS automatic shutdown if overload exceeds 110% of nominal @ 20 seconds and 125% @ 5 seconds
4/6 milliseconds (typical), including detection time
Active protection with automatic shutdown
BATTERY SYSTEM TYPE
BATTERY
TYPICAL RECHARGE TIME
PROTECTION
BATTERY QUANTITY
Hot swappable, sealed Valve Regulated Lead Acid (VRLA)
12V / 9.0 AH
4 hours (to 90% of full capacity)
Automatic self-test and discharge protection, Replace battery indicator
2 pcs , 2 pcs , 3 pcs , 4 pcs
NET WEIGHT(lbs)
DIMENSIONS WxDxH(inches)
30.4 lbs , 33.0 lbs , 55.0 lbs , 66.0 lbs
5.5" x 17.2" x 8.3" , 5.5" x 17.2" x 8.3" , 6.7" x 17.7" x 8.9" , 6.7" x 17.7" x 8.9"
COMMUNICATIONS RS-232
USB
SNMP
OPERATING SYSTEM
Standard (Detect battery low, schedule UPS on/off, AC Input/Output power status display)
Standard
Optional
Windows NT, Windows 2000/ME, Windows XP, Linux
ENVIRONMENT AMBIENT OPERATION
AUDIBLE NOISE @ 1 METER
STORAGE CONDITION
3,500 meters max. elevation, 0-95% RH non-condensing, 0-40°C
< 40 dBA , < 45 dBA
15,000 meters max. elevation, 0-95% RH non-condensing, 0-40°C
CERTIFICATIONS
UL, cUL, FCC Class A
1. Due to continuous product improvements, program specifications are subject to change without notice.