GE SG Series UPS

Delivering Best-in-Class Efficiency with eBoost Technology. The GE Energy SG Series is one of the most efficient and reliable Three Phase UPS Systems, providing best-in-class output performance and critical power protection for your data center needs.The SG Series UPS solutions are designed and optimized to provide high efficiency at partial load conditions. The SG Series UPS assures low input current harmonic distortion and best-in-class output voltage regulation and dynamic response. This helps customers save operational costs while implementing environmentally-friendly solutions.

Features & Benefits

• Up to 99% operating efficiency with written efficiency guarantees

• eBoost operation minimizes efficiency losses providing annual power & cooling savings up to $300k for 5MW data center

• eBoost line conditioning & voltage regulation via Bypass Inductor patented design

• Innovative product technologies that boost efficiency, reliability and lengthen battery life

• Top or bottom cable access

• Matching battery and maintenance bypass cabinet for easy configuration

• Front Maintainability Design reduces mean time to repair (MTTR)

• Scalable Solution

• Redundant Parallel Architecture (RPA) provides reliability, redundancy and scalability

• Parallel up to 6 UPS Modules

• Long history of experience with Redundant Parallel Architecture (RPA) which increases system reliability by eliminating single point of failures

GE SG Series 10-150 kVA high efficiency UPS Systems
TOPOLOGY True on-line, double conversion (VFI) with integral static switch and internal maintenance bypass
TECHNOLOGY Advanced IGBT with SVM strategy, microprocessor controlled at optimal switching frequency
OPERATING MODES True on-line double conversion, automatic bypass, frequency converter, RPA™ up to eight (8) units
OUTPUT POWER RATING kVA 10* 20* 30 40 50 80 100 120 150
Output Power Factor .8
Output Power Rating (kW) 8 16 24 32 40 64 80 96 120
Dimensions W x D x H (inches) 27 x 32 x 71 32 x 32 x 71 47 x 32 x 71
Weight w/o Batteries (lbs) 735 736 970 1147 1257 1489 1929 2006 2160
Noise Level dB(A) 60 63 65
Input Voltage (VAC) 480V, 3 Phase, 4 Wire w/ground (grounded WYE)
Input Voltage Range -20% to +15% (without battery discharge)
Input Frequency 60Hz +/-10%
Input Power Factor .8 PF (.93 with input filter) (.93 with 5th filter)
Output Voltage (sinusoidal) (VAC) 480V, 3 Phase, 4 Wire w/ground
Output Frequency 60Hz +/-10%
Output THD at Linear Load <2%
Output THD at Non-linear Load <3%
Crest Factor 3:1
Overload Capability on Inverter 125% @ 10 min., 150% @ 1 min.
Overload Capability on Automatic Bypass 200% @ 5 min., 110% continuously
OUTPUT VOLTAGE REGULATION
Static +/- 1%
0-100% Step Load +/- 3%
SYSTEM EFFICIENCY
100% Load 90.0 89.0 91.0 91.0 91.8 92.0 92.4 92.7 92.8
50% Load 89.5 88.7 90.5 90.5 92.2 92.5 92.9 93.1 93.3
Ambient Operating Temp. 32°-104°F (0°- 40°C)
Color RAL 9003 (white)
Classifications and Listing UL 1778 / IP20 / NEMA-PE-1 / ISO9001
RFI and Surge Protection EN 50091-2 / IEC 62040-2 / IEEE 587 B / FCC Class A compliance **
Standard Connectivity RS-232; programmable alarm contacts; programmable relays, SNMP (optional)
Warranty Twelve (12) months after commissioning or eighteen (18) months after shipment, whichever occurs first ***
1. Due to continuous product improvements, program specifications are subject to change without notice.

* Units available with internal batteries
** FCC Feature available as option
*** Extended Warranties available
GE SG Series 225-300 kVA high efficiency UPS Systems
TOPOLOGY True on-line, double conversion (VFI) with integral static switch and internal maintenance bypass
TECHNOLOGY Advanced IGBT with SVM strategy, microprocessor controlled at optimal switching frequency
OPERATING MODES True on-line double conversion, automatic bypass, frequency converter, RPA™ up to eight (8) units
OUTPUT POWER RATING kVA 225 300
Output Power Factor .8
Output Power Rating (kW) 180 240
Dimensions W x D x H (inches) 65 x 32 x 71
Weight w/o Batteries (lbs) 2756 3087
Noise Level dB(A) 67
Input Voltage (VAC) 480V, 3 Phase, 4 Wire w/ground (grounded WYE)
Input Voltage Range -20% to +15% (without battery discharge)
Input Frequency 60Hz +/-10%
Input Power Factor .8 PF (.93 with input filter)
Output Voltage (sinusoidal) (VAC) 480V, 3 Phase, 4 Wire w/ground
Output Frequency 60Hz +/-10%
Output THD at Linear Load <2%
Output THD at Non-linear Load <3% (IEC 62040)
Crest Factor >3:1
Overload Capability on Inverter 125% @ 10 min., 150% @ 1 min.
Overload Capability on Automatic Bypass 200% @ 5 min., 110% continuously
OUTPUT VOLTAGE REGULATION
Static +/- 1%
0-100% Step Load +/- 3%
SYSTEM EFFICIENCY
100% Load 92.4 92.7
50% Load 92.7 93.1
Ambient Operating Temp. 32°-104°F (0°- 40°C)
Color RAL 9003 (white)
Classifications and Listing UL 1778 / IP20 / NEMA-PE-1 / ISO9001
RFI and Surge Protection EN 50091-2 / IEC 62040-2 / IEEE 587 B / FCC Class A compliance *
Standard Connectivity RS-232; programmable alarm contacts; programmable relays, SNMP (optional)
Warranty Twelve (12) months after commissioning or eighteen (18) months after shipment, whichever occurs first **
1. Due to continuous product improvements, program specifications are subject to change without notice.

* FCC Feature available as option.
** Extended Warranties available.
GE SG Series 400-500 kVA high efficiency UPS Systems
TOPOLOGY True on-line, double conversion (VFI) with integral static switch and internal maintenance bypass
TECHNOLOGY Advanced IGBT with SVM strategy, microprocessor controlled at optimal switching frequency
OPERATING MODES True on-line double conversion, automatic bypass, frequency converter, RPA™ up to eight (8) units
OUTPUT POWER RATING kVA 400 500
Output Power Factor .8 .9
Output Power Rating (kW) 320 450
Dimensions W x D x H (inches) 81 x 33 x 77 81 x 33 x 77
Weight w/o Batteries (lbs) 4600 5100
Noise Level dB(A) 65
Input Voltage (VAC) 480V, 3 Phase, 4 Wire w/ground (grounded WYE)
Input Voltage Range -20% to +15% (without battery discharge)
Input Frequency 60Hz +/-10%
Input Power Factor .8 PF (.93 with input filter)
Output Voltage (sinusoidal) (VAC) 480V, 3 Phase, 4 Wire w/ground
Output Frequency 60Hz +/-10%
Output THD at Linear Load <2%
Output THD at Non-linear Load <3% (IEC 62040)
Crest Factor 3:1
Overload Capability on Inverter 125% @ 10 min., 150% @ 1 min.
Overload Capability on Automatic Bypass 200% @ 5 min., 110% continuously
OUTPUT VOLTAGE REGULATION
Static +/- 1%
0-100% Step Load +/- 3%
FAULT CLEARING CAPABILITY
Inverter - 220% for 100 msec. / 700% for 1.2 msec
Static Bypass - 100 KAIC
SYSTEM EFFICIENCY
100% Load 94.0 93.8
50% Load 94.2 94.4
Ambient Operating Temp. 32°-104°F (0°- 40°C)
Color RAL 9003 (white)
Classifications and Listing UL 1778 / IP20 / NEMA-PE-1 / ISO9001
RFI and Surge Protection EN 50091-2 / IEC 62040-2 / IEEE 587 B / FCC Class A compliance
Standard Connectivity RS-232; programmable alarm contacts; programmable relays, SNMP (optional)
Warranty Twelve (12) months after commissioning or eighteen (18) months after shipment, whichever occurs first *
1. Due to continuous product improvements, program specifications are subject to change without notice.

* Extended Warranties available
GE SG Series 750 kVA high efficiency UPS System
RECTIFIER CONFIGURATION 6-PULSE (5TH FILTER) 6-PULSE (5TH & 11TH FILTER) 12-PULSE (W/O FILTER) 12-PULSE (11TH FILTER)
POWER RATING
Output Capacity 750kVA / 675kW
POWER FACTOR
Output Power Factor 0.9
ENERGY EFFICIENCY
-50% Load 94.2% 94.1% 92.1% 92.0%
-100% Load 93.5% 93.4% 91.8% 91.7%
Heat Rejection (btu/hr) 161,435 162,897 207,100 208,634
PHYSICAL
Weight w/o batteries (lbs / kg) 9,557 / 4,335 9,696 / 4,398 11,091 / 5,031 11,230 / 5,094
Dimensions ( WxDxH) inches (mm) 146.5 x 35.4 x 76.7 (3,720 x 900 x 1,950) inverter & rectifier cabinets
INPUT
Input Voltage 480 V, 3-phase, 4-wire w/ground (3-wire available)
Voltage Range -15% to +10% (w/o battery discharge)
Frequency 60 Hz +/- 5%
Input THD <7% <5% <9% <4%
Input Power Factor 0.93 lagging 0.96 lagging 0.82 lagging 0.86 lagging
OUTPUT
Output Voltage 480 V, 3-phase, 4-wire w/ground
Frequency 60 Hz +/- 0.01% free running — 60 Hz +/- 4% synchronized with utility
Crest Factor 3:1
Voltage Regulation
Static +/- 1%
100% Step Load +/- 3%
Voltage Distortion
100% Linear Load 2% THD maximum
100% Non-Linear Load 3% THD maximum
Overload Capability
Inverter 125% for 10 minutes; 150% for 30 seconds
Bypass 110% continuous; 200% for 5 minutes
BATTERY
Compatibility VRLA or Wet cell
Float Voltage 545 VDC @ 68° F (20° C)
Recharge Time 10x discharge time (for battery runtime = 30 minutes)
GENERAL
Audible Noise 75 db(A) at 5 feet
Operating Temperature UPS: 32° to 104° F (0° - 40° C); Battery: 68° to 77° F (20° - 25° C)
Humidity 0-95%; non-condensing
Safety Classifications & Listings UL 1778 / IEC62040 / ISO 9001
Enclosure IP20 and NEMA-PE-1
Communication / Connectivity RS-232; programmable alarm contacts; programmable relays; SNMP (optional)
Color White (RAL 9003)
Warranty 12 months from start-up