Three Phase GE TLE Series 1
GE TLE Series UPS (225 to 1500kW)
« »
TLE Series UPS - 60 Hz, 225-1000kW

The TLE Series UPS brings the latest power conversion technology to the marketplace, using a three-level inverter design and a multi-mode architecture that makes real time decisions between premium protection mode and premium efficiency mode. The TLE Series UPS was developed using GE's Design for Six Sigma (DFSS) methodology to ensure that the product meets customer requirements for reliability and quality.

Features & Benefits

• Highly reliable and efficient tri-level conversion

• Automatic or manual multi-mode generation

• Up to 99% premium efficiency mode (filtered eBoost)

• Up to 97% premium protection mode (double conversion)

• Unity (1.0) Output Power Factor

• High (0.99) Input Power Factor

• Less than 5% Input Current Harmonic Distortion

• Small footprint

• Front access only design for maintenance

• "Cable saver" design to allow +/- 25% differential of cable lengths between UPS modules and the output parallel

GE TLE Series UPS
POWER RATING
Output Power Rating (kVA) 225 250 400 500 750 1000 1250 1500
Output Power Rating (kW) 225 250 400 500 750 1000 1250 1500
ENERGY USAGE
eBoost Mode Efficiency at 50% Load 98.2% 98.3% 98.2% 98.3% 98.2% 98.4% 98%+ 98%+
eBoost Mode Efficiency at 1000% Load 98.6% 98.8% 98.7% 98.8% 98.8% 98.9% 98%+ 98%+
eBoost Mode BTU/hr at 100% Load 10,901 10,361 17,977 20,722 31,082 37,951 87,041* 104,448*
Dbl Conv Mode EYciency at 50% Load 96.3% 96.5% 96.2% 96.4% 96.3% 96.4% 96%+ 96%+
Dbl Conv Mode EYciency at 100% Load 95.8% 96.0% 96.2% 96.3% 96.2% 96.2% 96%+ 96%+
Dbl Conv Mode BTU/hr at 100% Load 33,658 35,543 53,913 65,550 101,087 134,783 177,708* 213,250*
PHYSICALS
Dimensions, w x dp x h (in.) 43x34x75 64x34x75 107x34x75* 140x34x75* 173x34x75*
Weight, module only (lbs) 1,433 1,433 2,314 2,314 3,697* 4,837* 5,977* 6,577*
INPUT
Voltage 480/277V 3ph 4w + gnd
Topology IGBT Rectifier
Dual Input Capable Remove internal jumper cables for separate inputs to Rectifier & Static Bypass
Voltage Range (w/o battery discharge) -15% to +15%
Power Factor (lagging) 0.99
Current THD <5.0%
Frequency 60 Hz +/- 10%
OUTPUT
Voltage 480/277V 3ph 4w + grd
Topology PWM 3-Level IGBT Inverter
Frequency 60 Hz +/- 10%
Crest Factor 3:1
Static Voltage Regulation +/- 1%
100% Step Load Voltage Regulation +/- 3%
100% Linear Load Voltage Distortion <3.0% THD maximum
100% Non-Linear Load Voltage Distortion <5.0% THD maximum
eBoost Transfer Time < 2msec transfer to Inverter, within ITI/CBEMA voltage compliance curve
Overload Capability / Inverter 125% / 1 min ; 150% / 30 sec
Overload Capability / Static Bypass 110% continuous ; 150% for 1 minute
BATTERY PLANT
Compatible Technologies VRLA, Wet Cell, NiCad, and/or DC Flwheel option
Float Voltage 540 VDC , 240 cell system
Recharge Time 10X discharge time (at 30min battery runtime)
GENERAL
Audible Noise 75 db(A) at 5 ft 76 db(A) at 5 ft 77 db(A) at 5 ft 78 db(A) at 5 ft
Audible Noise (eBoost Mode) 65 db(A) at 5 ft 66 db(A) at 5 ft 67 db(A) at 5 ft 68 db(A) at 5 ft
Ambient Operating Temp UPS Module: 32 to 104 degrees F (0-40 degrees C)
Humidity 0-95% non-condensing
Listings / Registrations ETL as tested to UL1778 / IEC62040 / ISO 9001
Enclosure IP20 and NEMA PE-1
RFI / Surge Protection EN50091-2 / IEC 62040-2 / IEEE 587B / FCC Class A Part B Compliance. Special FCC Filters available
Communication / Connectivity RS232, programmable contacts, programmable relays, iUPSguard, optional SNMP & Modbus
Color < RAL 9005 Black
Warranty 12mo after startup or 18mo after shipment (whichever first). Extended warranties available.
1. Due to continuous product improvements, program specifications are subject to change without notice.

* = estimated data. Consult factory for updated information.
GE TLE Series UPS
POWER RATING
Output Power Rating (kVA) 160 200 320 400 600 800 1000 1200
Output Power Rating (kW) 160 200 320 400 600 800 1000 1200
ENERGY USAGE
eBoost Mode Efficiency at 50% Load >98% >98% >98% >98% >98% >98% >98% >98%
eBoost Mode Efficiency at 1000% Load >98% >98% >98% >98% >98% >98% >98% >98%
eBoost Mode BTU/hr at 100% Load 11,141* 13,926* 22,282* 27,853* 41,779* 55,706* 69,632* 83,558*
Dbl Conv Mode EYciency at 50% Load >96% >96% >96% >96% >96% >96% >96% >96%
Dbl Conv Mode EYciency at 100% Load >95% >95% >95% >95% >95% >95% >95% >95%
Dbl Conv Mode BTU/hr at 100% Load 28,733* 35,916* 57,465* 71,832* 107,747* 143,663* 179,578* 215,494*
PHYSICALS
Dimensions, w x dp x h (in.) 43x34x75 64x34x75 107x34x75* 140x34x75* 173x34x75*
Weight, module only (lbs) 1,433 1,433 2,314 2,314 3,697* 4,837* 5,977* 6,577*
INPUT
Voltage 400/230V 3ph 4w + gnd
Topology IGBT Rectifier
Dual Input Capable Remove internal jumper cables for separate inputs to Rectifier & Static Bypass
Voltage Range (w/o battery discharge) -15% to +15%
Power Factor (lagging) 0.99
Current THD <3.0%
Frequency 45-65Hz
OUTPUT
Voltage 400/230V 3ph 4w + grd
Topology PWM 3-Level IGBT Inverter
Frequency 50/60Hz
Crest Factor 3:1
Static Voltage Regulation +/- 1%
100% Step Load Voltage Regulation +/- 3%
100% Linear Load Voltage Distortion <1.5% THD maximum
100% Non-Linear Load Voltage Distortion <5.0% THD maximum
eBoost Transfer Time < 2msec from Bypass to Inverter, within ITI/CBEMA voltage compliance curve
Overload Capability / Inverter 125% / 1 min ; 150% / 30 sec
Overload Capability / Static Bypass 110% continuous ; 200% for 5 minutes
BATTERY PLANT
Compatible Technologies VRLA, Wet Cell, NiCad, and/or DC Flwheel option
Float Voltage 540 VDC , 240 cell system
Recharge Time 10X discharge time (at 30min battery runtime)
GENERAL
Audible Noise 75 db(A) at 5 ft 76 db(A) at 5 ft 77 db(A) at 5 ft 78 db(A) at 5 ft
Audible Noise (eBoost Mode) 65 db(A) at 5 ft 66 db(A) at 5 ft 67 db(A) at 5 ft 68 db(A) at 5 ft
Ambient Operating Temp UPS Module: 32 to 104 degrees F (0-40 degrees C)
Humidity 0-95% non-condensing
Listings / Registrations ETL as tested to UL1778 / IEC62040 / ISO 9001
Enclosure IP20 and NEMA PE-1
RFI / Surge Protection EN50091-2 / IEC 62040-2 / IEEE 587B / FCC Class A Part B Compliance. Special FCC Filters available
Communication / Connectivity RS232, programmable contacts, programmable relays, iUPSguard, optional SNMP & Modbus
Color < RAL 9005 Black
Warranty 12mo after startup or 18mo after shipment (whichever first). Extended warranties available.
1. Due to continuous product improvements, program specifications are subject to change without notice.

* = estimated data. Consult factory for updated information.