GE GT Series UPS
With the Digital Energy GT Series, your mission critical equipment is protected from any fluctuation in your power source, enabling you to concentrate on your core activities. The GT Series is a true VFI (Voltage & Frequency Independent) on-line double conversion, transformerless, intelligent and high performance UPS.
This UPS provides critical power protection to suit a wide range of IT Networks, Telecom and other applications. The GT Series is easy to install and service, and is designed for maximum site flexibility. With an attractively designed modern common tower and/or 19-inch rack mount cabinet, the UPS can adapt as network configurations adapt. Both the power and redundancy of the system can be expanded by adding units (N+2) to create a parallel system.
For communication, the GT Series is equipped with RS-232 and contact interface as standard; a web-enabled SNMP card is available as an option. Operation from remote or unmanned sites is simple to coordinate with standard remote monitoring functionality. No load shutdown, automatic frequency detection, settable minimum start-up runtime and extended runtime availability with optional battery packs are additional features of the GT Series UPS.
(3kVA) Features & Benefits
• Fully digitized microprocessor control - Modern, reliable platform
• Matching battery cabinets - Extended runtime for all models
• Programmable outlet - Selectable shutdown for lower priority loads
• Modern design and low audible noise - Fits well into an office environment
• Cold start - UPS can start up without utility present
• High visibility graphic display - Immediate access to UPS status
(5-10kVA) Features & Benefits
• Tower and/or rack design - Maximum site flexibility; all necessary parts delivered in packing box
• Backfeed protection as standard - Ensuring site safety without additional installation requirements
• Matching battery cabinets - Extended runtime for all models
• Programmable load shutdown - Remote on/off switching for isolated or unmanned sites
• Hot swappable batteries - Easy battery replacement without disconnecting the load
• Cold start - UPS can start up without utility present
• Multiple PDU options -Installable and pluggable load connection possibilities
Product Specifications
GT Series UPS - UL Listed (3kVA)
• Single Phase Output Voltage - 110V with 208V optional on 3kVA units
• Wide input voltage window 80-138V - Minimizes battery use, prolongs battery life
• Pulse Width Modulation technology - Eliminates the need to oversize the UPS
• Internal automatic bypass switch - Continuous power supply to the load even if the UPS is overloaded
• Low input distortion - Prevents disturbance to nearby electrical equipment
GT Series UPS - UL Listed (5-10kVA)
• Single Phase Output Voltages - 120/208V
• Wide input voltage window 80-138V - Minimizes battery use, prolongs battery life
• Redundant and paralleling capability - UPS capacity can be increased as site requirements require at no extra cost
• Internal automatic bypass switch - Continuous power supply to the load even if the UPS is overloaded
• No load shutdown - Prevents deep battery discharge al low loads
• Frequency conversion 60/50Hz - Automatic frequency detection
Technical Specifications
MODEL NUMBER
RATING (VA/W)
BATTERY (V/Ah)
BACKUP TIME @50% LOAD (25°C)
ADDITIONAL BATTERIES OPTIONS
DIMENSIONS (HxWxD)
NET WGT INCL. BATTERIES (kg / lbs)
INPUT VOLTAGE @ 100% LOAD (VAC)
INPUT FREQUENCY (Hz)*
OUTPUT VOLTAGE
NUMBER OF OUTLETS
SNMP COMPATIBILITY
CORE VOLTAGE
PWM (PULSE WIDTH MODULATION)
MAINTENANCE BYPASS
INTERNAL BATTERIES
INPUT PERFORMANCE RANGE
OUTPUT PERFORMANCE
OUTPUT THD LOAD
VOLTAGE REGULATION LOAD
OVERLOAD CAPABILITY
EFFICIENCY
COMMUNICATIONS INTERFACE
COLOR
OPERATING TEMPERATURE
RELATIVE HUMIDITY
AUDIBLE NOISE AT 3.3FT (1 METER)
SAFETY
EMC
ENCLOSURE
GT3000R , GT3000T208
3000 / 2400 , 3000 / 2400
2000VA/1200W , 3000VA/1800W
14 min.
Yes
13.2x43.9x50.3cm (5.2x17.3x19.8in) , 37.3x14x42.4cm (14.7x5.5x16.7in)
34 / 74.9 , 30 / 66
80-138 , 160-275
50/60
100/110 , 160/208
(4)NEMA 5-15R , (4)NEMA 6-20R
(1)NEMA L5-20R , (1)NEMA L6-20R
(1)NEMA L5-30R
Yes
120
Yes
Yes
Yes
Voltage (-33 to +17%); Frequency (55 to 65 Hz)
Non-Linear (<6%); Linear (<3%)
Static (2%); 0-100% Step (8%)
150% for 30 seconds
>87%
RS-232, Plug and Play, open collector alarm contacts
Front bezel: Aluminum Grey (RAL9006); Cabinet: White (RAL9010)
32° F - 104° F (0° C - 40° C)
95% non-condensing
47 dBA , 42 dBA
UL 1778, CSA22.2-107, IEEE 62.41 CAT. A Lightning Safety
FCC Class B (1kVA), FCC Class A (remaining), CISPR PUB. 22 Class A
NEMA1
1. Due to continuous product improvements, program specifications are subject to change without notice.
Technical Specifications (5-10kVA)
MODEL NUMBER
RATINGS:
Power Rating Depending on Input Voltage
100V / 200V
110V / 220V
115V / 230V
120V / 208V
120V / 240V
127V / 220V
Input Thermal Circuit Breaker (A)
Internal Input Fuse 250V, Slow (A) Qty
INPUT CONVERTER
AC Input Voltage
AC Input Voltage Range
Input Current Waveform
Input Current (A) at Nominal Input Voltage
Input Power Factor
Input Frequency Range
Input phase (L1 to L2)
Inrush Current
OUTPUT CONVERTER
AC Output Voltage
AC Output Voltage Tolerance
Output Frequency Range
Output Waveform
Harmonic Distortion
Power Factor at Nominal Input Voltage
Crest Factor (Peak to RMS Current)
Capacity Appliance Outlets
BYPASS
AC Input Voltage Range
Frequency Tracking Rate
Frequency Tracking Range
Typical Transfer Time, msec
OVERLOAD CAPABILITY
Overload Behavior During Battery Operation
Overload Behavior During Bypass Operation
BATTERIES (RATINGS GIVEN FOR 25º C)
Nominal Voltage(Vdc)
Qty / Ah (In Battery Kit & Battery Ext. Pack)
Type
Recharge Current
Battery Recharge Time (Batt. Discharged at 100% Load)
GENERAL
Weight UPS
Dimensions UPS (HxWxD)
Weight Battery Pack
Dimensions Battery Pack
Enclosure / Protection
Mounting
ENVIROMENT
Safety Compliance
Electromagnetic Compatibility
Ambient Temperature
Audible Noise at 3.3 ft.
Max. Relative Humidity
Color
GT5000 RT
GT6000 RT
GT8000 RT
GT10000 RT
VA/W
VA/W
VA/W
VA/W
4000 / 3400
4500 / 3800
5000 / 4000
4800 / 4200
5000 / 4200
4800 / 4200
30
30
Nominal:120/208V
100/(173-200), 110/(190-220), 115/(198-230), 120/(208-240), 127/(220) V
Sine Wave
20
>0.97
40 - 70 Hz
120° / 180° / 240° ±10°
40
100 / 110 / 115 / 120 / 127 V (selectable)
L-N ± 3%; L1-L2 ± 5%
nominal ± 5% with mains synchronizing
Sine wave
< 3% with linear load, < 5% with non-linear full load
0.87
≤ 3 : 1
with 55A Terminal Block
± 15% of selected output voltage
1Hz/s
± 5% of selected frequency
0
130% for 10 seconds 200% for 2 seconds
Depends on rating of thermal circuit breaker (TCB)
125% of TCB value for 200 seconds
200% of TCB value for 10 seconds
300% of TCB value for 4 seconds
144
12 pcs / 8Ah
REW45-12 FR
1A
6 hours for 90% capacity
30.3 Kg (67 lbs)
176x430x592 mm (6.9x16.9x22.55 in)
43 Kg (94.7 lbs)
87x430x592 mm (3.47x16.9x2255 in)
steel-plastic / IP20
Rackmount or Tower mount with same unit
UL 1778
EMI: FCC CFR47 Part 15, class A, ESD:
IEC61000-4-2, level 4
RS: IEC61000-4-3, level 3, EFT: IEC61000-4-4,
level 4, Surge: IEC61000-4-5, level 3
ANSI C62.41 (IEEE587) Category A
(level 3) & B (level 1)
0 to +40ºC
<55 dB(A), load and temperature dependent
90% (non-condensing)
Black - RAL 9005
4800 / 3400
5400 / 3800
60000 / 4200
5200 / 4200
6000 / 4200
5200 / 4200
30
30
Nominal:120/208V
100/(173-200), 110/(190-220), 115/(198-230), 120/(208-240), 127/(220) V
Sine Wave
20
>0.97
40 - 70 Hz
120° / 180° / 240° ±10°
40
100 / 110 / 115 / 120 / 127 V (selectable)
L-N ± 3%; L1-L2 ± 5%
nominal ± 5% with mains synchronizing
Sine wave
< 3% with linear load, < 5% with non-linear full load
0.8
≤ 3 : 1
with 55A Terminal Block
± 15% of selected output voltage
1Hz/s
± 5% of selected frequency
0
130% for 10 seconds 200% for 2 seconds
Depends on rating of thermal circuit breaker (TCB)
125% of TCB value for 200 seconds
200% of TCB value for 10 seconds
300% of TCB value for 4 seconds
144
12 pcs / 8Ah
REW45-12 FR
1A
6 hours for 90% capacity
30.3 Kg (67 lbs)
176x430x592 mm (6.9x16.9x22.55 in)
43 Kg (94.7 lbs)
87x430x592 mm (3.47x16.9x2255 in)
steel-plastic / IP20
Rackmount or Tower mount with same unit
UL 1778
EMI: FCC CFR47 Part 15, class A, ESD:
IEC61000-4-2, level 4
RS: IEC61000-4-3, level 3, EFT: IEC61000-4-4,
level 4, Surge: IEC61000-4-5, level 3
ANSI C62.41 (IEEE587) Category A
(level 3) & B (level 1)
0 to +40ºC
<55 dB(A), load and temperature dependent
90% (non-condensing)
Black - RAL 9005
6400 / 6400
7200 / 7200
8000 / 6900
8000 / 6900
8000 / 8000
8000 / 6900
60
30/2
Nominal:120/208V
100/(173-200), 110/(190-220), 115/(198-230), 120/(208-240), 127/(220) V
Sine Wave
40
>0.97
40 - 70 Hz
120° / 180° / 240° ±10°
40
100 / 110 / 115 / 120 / 127 V (selectable)
L-N ± 3%; L1-L2 ± 5%
nominal ± 5% with mains synchronizing
Sine wave
< 3% with linear load, < 5% with non-linear full load
0.86
≤ 3 : 1
with 55A Terminal Block
± 15% of selected output voltage
1Hz/s
± 5% of selected frequency
0
130% for 1 minute
200% for 5 seconds
Overload protection
110% of TCB value for 300 seconds
130% of TCB value for 30 seconds
200% of TCB value for 5 seconds
288
24 / 8Ah
REW45-12 FR
1A
3 hours for 90% capacity
49.3 Kg (109 lbs)
267x430x660 mm (10.5x16.9x26 in)
91 Kg (200.4 lbs)
173x430x660 mm (6.8x16.9x26 in)
steel-plastic / IP20
Rackmount or Tower mount with same unit
UL 1778
EMI: FCC CFR47 Part 15, class A, ESD:
IEC61000-4-2, level 4
RS: IEC61000-4-3, level 3, EFT: IEC61000-4-4,
level 4, Surge: IEC61000-4-5, level 3
ANSI C62.41 (IEEE587) Category A
(level 3) & B (level 1)
0 to +40ºC
<55 dB(A), load and temperature dependent
90% (non-condensing)
Black - RAL 9005
8000 / 6400
9000 / 7200
8700 / 8000
8700 / 8000
10000 / 8000
8700 / 8000
60
30/2
Nominal:120/208V
100/(173-200), 110/(190-220), 115/(198-230), 120/(208-240), 127/(220) V
Sine Wave
40
>0.97
40 - 70 Hz
120° / 180° / 240° ±10°
40
100 / 110 / 115 / 120 / 127 V (selectable)
L-N ± 3%; L1-L2 ± 5%
nominal ± 5% with mains synchronizing
Sine wave
< 3% with linear load, < 5% with non-linear full load
0.92
≤ 3 : 1
with 55A Terminal Block
± 15% of selected output voltage
1Hz/s
± 5% of selected frequency
0
130% for 1 minute
200% for 5 seconds
Overload protection
110% of TCB value for 300 seconds
130% of TCB value for 30 seconds
200% of TCB value for 5 seconds
288
24 / 8Ah
REW45-12 FR
1A
3 hours for 90% capacity
49.3 Kg (109 lbs)
267x430x660 mm (10.5x16.9x26 in)
91 Kg (200.4 lbs)
173x430x660 mm (6.8x16.9x26 in)
steel-plastic / IP20
Rackmount or Tower mount with same unit
UL 1778
EMI: FCC CFR47 Part 15, class A, ESD:
IEC61000-4-2, level 4
RS: IEC61000-4-3, level 3, EFT: IEC61000-4-4,
level 4, Surge: IEC61000-4-5, level 3
ANSI C62.41 (IEEE587) Category A
(level 3) & B (level 1)
0 to +40ºC
<55 dB(A), load and temperature dependent
90% (non-condensing)
Black - RAL 9005
1. Due to continuous product improvements, program specifications are subject to change without notice.