top of page
gtseries-site1.png

GT Series 1-3kVA UPS Rack

GE GT Series UPS

With the Digital Energy GT Series, your mission critical equipment is protected from any fluctuation in your power source, enabling you to concentrate on your core activities. The GT Series is a true VFI (Voltage & Frequency Independent) on-line double conversion, transformerless, intelligent and high performance UPS.

This UPS provides critical power protection to suit a wide range of IT Networks, Telecom and other applications. The GT Series is easy to install and service, and is designed for maximum site flexibility. With an attractively designed modern common tower and/or 19-inch rack mount cabinet, the UPS can adapt as network configurations adapt. Both the power and redundancy of the system can be expanded by adding units (N+2) to create a parallel system.

For communication, the GT Series is equipped with RS-232 and contact interface as standard; a web-enabled SNMP card is available as an option. Operation from remote or unmanned sites is simple to coordinate with standard remote monitoring functionality. No load shutdown, automatic frequency detection, settable minimum start-up runtime and extended runtime availability with optional battery packs are additional features of the GT Series UPS.

(3kVA) Features & Benefits

• Fully digitized microprocessor control - Modern, reliable platform

• Matching battery cabinets - Extended runtime for all models

• Programmable outlet - Selectable shutdown for lower priority loads

• Modern design and low audible noise - Fits well into an office environment

• Cold start - UPS can start up without utility present

• High visibility graphic display - Immediate access to UPS status

(5-10kVA) Features & Benefits

• Tower and/or rack design - Maximum site flexibility; all necessary parts delivered in packing box

• Backfeed protection as standard - Ensuring site safety without additional installation requirements

• Matching battery cabinets - Extended runtime for all models

• Programmable load shutdown - Remote on/off switching for isolated or unmanned sites

• Hot swappable batteries - Easy battery replacement without disconnecting the load

• Cold start - UPS can start up without utility present

• Multiple PDU options -Installable and pluggable load connection possibilities

Product Specifications

GT Series UPS - UL Listed (3kVA)


• Single Phase Output Voltage - 110V with 208V optional on 3kVA units


• Wide input voltage window 80-138V - Minimizes battery use, prolongs battery life


• Pulse Width Modulation technology - Eliminates the need to oversize the UPS


• Internal automatic bypass switch - Continuous power supply to the load even if the UPS is overloaded


• Low input distortion - Prevents disturbance to nearby electrical equipment

GT Series UPS - UL Listed (5-10kVA)


• Single Phase Output Voltages - 120/208V


• Wide input voltage window 80-138V - Minimizes battery use, prolongs battery life


• Redundant and paralleling capability - UPS capacity can be increased as site requirements require at no extra cost


• Internal automatic bypass switch - Continuous power supply to the load even if the UPS is overloaded


• No load shutdown - Prevents deep battery discharge al low loads


• Frequency conversion 60/50Hz - Automatic frequency detection

Technical Specifications

MODEL NUMBER

RATING (VA/W)

BATTERY (V/Ah)

BACKUP TIME @50% LOAD (25°C)

ADDITIONAL BATTERIES OPTIONS

DIMENSIONS (HxWxD)

NET WGT INCL. BATTERIES (kg / lbs)

INPUT VOLTAGE @ 100% LOAD (VAC)

INPUT FREQUENCY (Hz)*

OUTPUT VOLTAGE

NUMBER OF OUTLETS

SNMP COMPATIBILITY

CORE VOLTAGE

PWM (PULSE WIDTH MODULATION)

MAINTENANCE BYPASS

INTERNAL BATTERIES

INPUT PERFORMANCE RANGE

OUTPUT PERFORMANCE

OUTPUT THD LOAD

VOLTAGE REGULATION LOAD

OVERLOAD CAPABILITY

EFFICIENCY

COMMUNICATIONS INTERFACE

COLOR

OPERATING TEMPERATURE

RELATIVE HUMIDITY

AUDIBLE NOISE AT 3.3FT (1 METER)

SAFETY

EMC

ENCLOSURE

GT3000R , GT3000T208

3000 / 2400 , 3000 / 2400

2000VA/1200W , 3000VA/1800W

14 min.

Yes

13.2x43.9x50.3cm (5.2x17.3x19.8in) , 37.3x14x42.4cm (14.7x5.5x16.7in)

 

 

34 / 74.9 , 30 / 66

80-138 , 160-275

50/60

100/110 , 160/208

(4)NEMA 5-15R , (4)NEMA 6-20R
(1)NEMA L5-20R , (1)NEMA L6-20R
(1)NEMA L5-30R

Yes

120

Yes

Yes

Yes

Voltage (-33 to +17%); Frequency (55 to 65 Hz)

Non-Linear (<6%); Linear (<3%)

Static (2%); 0-100% Step (8%)

150% for 30 seconds

>87%

RS-232, Plug and Play, open collector alarm contacts

Front bezel: Aluminum Grey (RAL9006); Cabinet: White (RAL9010)

32° F - 104° F (0° C - 40° C)

95% non-condensing

47 dBA , 42 dBA

UL 1778, CSA22.2-107, IEEE 62.41 CAT. A Lightning Safety

FCC Class B (1kVA), FCC Class A (remaining), CISPR PUB. 22 Class A

NEMA1

1. Due to continuous product improvements, program specifications are subject to change without notice.

Technical Specifications (5-10kVA)

MODEL NUMBER

RATINGS:

Power Rating Depending on Input Voltage

100V / 200V

110V / 220V

115V / 230V

120V / 208V

120V / 240V

127V / 220V

Input Thermal Circuit Breaker (A)

Internal Input Fuse 250V, Slow (A) Qty

INPUT CONVERTER

AC Input Voltage

AC Input Voltage Range

Input Current Waveform

Input Current (A) at Nominal Input Voltage

Input Power Factor

Input Frequency Range

Input phase (L1 to L2)

Inrush Current

OUTPUT CONVERTER

AC Output Voltage

AC Output Voltage Tolerance

Output Frequency Range

Output Waveform

Harmonic Distortion

Power Factor at Nominal Input Voltage

Crest Factor (Peak to RMS Current)

Capacity Appliance Outlets

BYPASS

AC Input Voltage Range

Frequency Tracking Rate

Frequency Tracking Range

Typical Transfer Time, msec

OVERLOAD CAPABILITY

Overload Behavior During Battery Operation

Overload Behavior During Bypass Operation

BATTERIES (RATINGS GIVEN FOR 25º C)

Nominal Voltage(Vdc)

Qty / Ah (In Battery Kit & Battery Ext. Pack)

Type

Recharge Current

Battery Recharge Time (Batt. Discharged at 100% Load)

GENERAL

Weight UPS

Dimensions UPS (HxWxD)

Weight Battery Pack

Dimensions Battery Pack

Enclosure / Protection

Mounting

ENVIROMENT 

Safety Compliance

Electromagnetic Compatibility

Ambient Temperature

Audible Noise at 3.3 ft.

Max. Relative Humidity

Color

GT5000 RT

GT6000 RT

GT8000 RT

GT10000 RT

VA/W

VA/W

VA/W

VA/W

4000 / 3400

4500 / 3800

5000 / 4000

4800 / 4200

5000 / 4200

4800 / 4200

30

30

 

 

Nominal:120/208V

100/(173-200), 110/(190-220), 115/(198-230), 120/(208-240), 127/(220) V

Sine Wave

20

>0.97

40 - 70 Hz

 

120° / 180° / 240° ±10°

40

100 / 110 / 115 / 120 / 127 V (selectable)

L-N ± 3%; L1-L2 ± 5%

nominal ± 5% with mains synchronizing

Sine wave

< 3% with linear load, < 5% with non-linear full load

0.87

≤ 3 : 1

with 55A Terminal Block

± 15% of selected output voltage

1Hz/s

± 5% of selected frequency

0

130% for 10 seconds 200% for 2 seconds

Depends on rating of thermal circuit breaker (TCB)
125% of TCB value for 200 seconds
200% of TCB value for 10 seconds
300% of TCB value for 4 seconds

144

12 pcs / 8Ah

REW45-12 FR

1A

6 hours for 90% capacity

30.3 Kg (67 lbs)

176x430x592 mm (6.9x16.9x22.55 in)

43 Kg (94.7 lbs)

87x430x592 mm (3.47x16.9x2255 in)

steel-plastic / IP20

Rackmount or Tower mount with same unit

UL 1778

EMI: FCC CFR47 Part 15, class A, ESD:
IEC61000-4-2, level 4
RS: IEC61000-4-3, level 3, EFT: IEC61000-4-4,
level 4, Surge: IEC61000-4-5, level 3
ANSI C62.41 (IEEE587) Category A
(level 3) & B (level 1)

0 to +40ºC

<55 dB(A), load and temperature dependent

90% (non-condensing)

Black - RAL 9005

4800 / 3400

5400 / 3800

60000 / 4200

5200 / 4200

6000 / 4200

5200 / 4200

30

30

 

Nominal:120/208V

100/(173-200), 110/(190-220), 115/(198-230), 120/(208-240), 127/(220) V

Sine Wave

20

>0.97

40 - 70 Hz

120° / 180° / 240° ±10°

40

100 / 110 / 115 / 120 / 127 V (selectable)

L-N ± 3%; L1-L2 ± 5%

nominal ± 5% with mains synchronizing

Sine wave

< 3% with linear load, < 5% with non-linear full load

0.8

≤ 3 : 1

with 55A Terminal Block

± 15% of selected output voltage

1Hz/s

± 5% of selected frequency

0

130% for 10 seconds 200% for 2 seconds

Depends on rating of thermal circuit breaker (TCB)
125% of TCB value for 200 seconds
200% of TCB value for 10 seconds
300% of TCB value for 4 seconds

144

12 pcs / 8Ah

REW45-12 FR

1A

6 hours for 90% capacity

30.3 Kg (67 lbs)

176x430x592 mm (6.9x16.9x22.55 in)

43 Kg (94.7 lbs)

87x430x592 mm (3.47x16.9x2255 in)

steel-plastic / IP20

Rackmount or Tower mount with same unit

UL 1778

EMI: FCC CFR47 Part 15, class A, ESD:
IEC61000-4-2, level 4
RS: IEC61000-4-3, level 3, EFT: IEC61000-4-4,
level 4, Surge: IEC61000-4-5, level 3
ANSI C62.41 (IEEE587) Category A
(level 3) & B (level 1)

0 to +40ºC

<55 dB(A), load and temperature dependent

90% (non-condensing)

Black - RAL 9005

6400 / 6400

7200 / 7200

8000 / 6900

8000 / 6900

8000 / 8000

8000 / 6900

60

30/2

 

Nominal:120/208V

100/(173-200), 110/(190-220), 115/(198-230), 120/(208-240), 127/(220) V

Sine Wave

40

>0.97

40 - 70 Hz

120° / 180° / 240° ±10°

40

100 / 110 / 115 / 120 / 127 V (selectable)

L-N ± 3%; L1-L2 ± 5%

nominal ± 5% with mains synchronizing

Sine wave

< 3% with linear load, < 5% with non-linear full load

0.86

≤ 3 : 1

with 55A Terminal Block

± 15% of selected output voltage

1Hz/s

± 5% of selected frequency

0

130% for 1 minute
200% for 5 seconds

Overload protection
110% of TCB value for 300 seconds
130% of TCB value for 30 seconds
200% of TCB value for 5 seconds

288

24 / 8Ah

REW45-12 FR

1A

3 hours for 90% capacity

49.3 Kg (109 lbs)

267x430x660 mm (10.5x16.9x26 in)

91 Kg (200.4 lbs)

173x430x660 mm (6.8x16.9x26 in)

steel-plastic / IP20

Rackmount or Tower mount with same unit

UL 1778

EMI: FCC CFR47 Part 15, class A, ESD:
IEC61000-4-2, level 4
RS: IEC61000-4-3, level 3, EFT: IEC61000-4-4,
level 4, Surge: IEC61000-4-5, level 3
ANSI C62.41 (IEEE587) Category A
(level 3) & B (level 1)

0 to +40ºC

<55 dB(A), load and temperature dependent

90% (non-condensing)

Black - RAL 9005

8000 / 6400

9000 / 7200

8700 / 8000

8700 / 8000

10000 / 8000

8700 / 8000

60

30/2

 

Nominal:120/208V

100/(173-200), 110/(190-220), 115/(198-230), 120/(208-240), 127/(220) V

Sine Wave

40

>0.97

40 - 70 Hz

120° / 180° / 240° ±10°

40

100 / 110 / 115 / 120 / 127 V (selectable)

L-N ± 3%; L1-L2 ± 5%

nominal ± 5% with mains synchronizing

Sine wave

< 3% with linear load, < 5% with non-linear full load

0.92

≤ 3 : 1

with 55A Terminal Block

± 15% of selected output voltage

1Hz/s

± 5% of selected frequency

0

130% for 1 minute
200% for 5 seconds

Overload protection
110% of TCB value for 300 seconds
130% of TCB value for 30 seconds
200% of TCB value for 5 seconds

288

24 / 8Ah

REW45-12 FR

1A

3 hours for 90% capacity

49.3 Kg (109 lbs)

267x430x660 mm (10.5x16.9x26 in)

91 Kg (200.4 lbs)

173x430x660 mm (6.8x16.9x26 in)

steel-plastic / IP20

Rackmount or Tower mount with same unit

UL 1778

EMI: FCC CFR47 Part 15, class A, ESD:
IEC61000-4-2, level 4
RS: IEC61000-4-3, level 3, EFT: IEC61000-4-4,
level 4, Surge: IEC61000-4-5, level 3
ANSI C62.41 (IEEE587) Category A
(level 3) & B (level 1)

0 to +40ºC

<55 dB(A), load and temperature dependent

90% (non-condensing)

Black - RAL 9005

1. Due to continuous product improvements, program specifications are subject to change without notice.

bottom of page