top of page
vhseries-site2.png

VH Series Rackmount UPS

GE VH Series UPS

The Digital Energy™ VH Series UPS connects between the utility and your critical load, helping ensure that when the utility drops or fails, your load continues to receive a clean, constant and reliable power supply. The VH Series UPS is ideal for protection against utility variances and failures for PC, telecom, laboratory, industrial and critical process loads.

The VH Series is a true Voltage and Frequency Independent (VFI) on line, double conversion UPS providing secure power for business-critical applications. With a tower and/or rack mount design, the UPS adapts to adjusting network configurations as facility load requirements change. Delivering 0.9 output power factor, a Mean Time Between Failure (MTBF) of 730,000 hours and a three year warranty standard on UPS and battery, the user can be assured of a high performance, high power and highly reliable level of power protection.

Features & Benefits

• Voltage and Frequency Independent (VFI) double conversion


• Failsafe bypass


• Comprehensive warranty and high MTBF


• Automatic bypass switch


• Easy, fast battery replacement


• Large charge capacity and boost/float charging


• Tower and rackmount, small footprint


• Unique high peak load handling


• Frequency converter


• High output power factor (0.9)


• Standard USB connection


• Range of communication options

Product Specifications

• Unique failsafe internal bypass - Continued operation even with overload or over-temperature


• 2U design for all ratings - Small footprint; parts supplied for tower or rack assembly


• Hot swappable batteries - Simple, fast battery replacement without disruption to the load


• Matching battery cabinets - Longer battery life available with the addition of extra battery cabinet(s)


• Superior battery management - Provides protection to the battery and extends the battery life


• Remote monitoring - Easy access and control even for unmanned or isolated sites


• MTBF >730,000 hours - Proven reliability


• Increased power handling - 0.9 output power factor delivers more actual power to the load

Technical Specifications

VH SERIES

INPUT CONVERTER

OUTPUT CONVERTER

BYPASS

BATTERIES

(rating given for 77°F)

GENERAL

ENVIROMENT

 

 

Voltage Amperes (VA) with computer type load
Watts (W) with resistive load

AC input voltage
Input current waveform
Input current (A) at nominal input voltage
Input power factor
Input frequency range
Inrush current

 

AC output voltage
Output frequency
Output waveform
Power Factor
Capacity appliance outlets

AC input voltage range
Frequency tracking rate
Frequency tracking range
Phase difference
Typical transfer time, msec

 

Nominal voltage (Vdc)
Number / Ah batteries
Type
Service life
Recharge current
Battery recharge time (batt. discharge at 100% load)
Runtime in minutes at typical load (75%)

Weight UPS (lbs/kg)
Dimensions UPS (HxWxD)

 

Safety
Electromagnetic compatibility
Ambient temperature
Audible noise at 1 meter
Max. relative humidity

700 , 1000 , 1500 , 2000

700 , 1000 , 1500 , 1920
630 , 900 , 1350 , 1740

60 - 140V
Sinusoidal, EN 61000-3-2(IEC 555-2) compliant
6.6 , 9.1 , 13.9 , 16

 

1
45-66
none

100 / 110 / 115 / 120 / 127V (selectable)
Auto selectable or 50/60 Hz, front selectable
Sine wave
0.9
max. 20A per outlet (+1 high power outlet max. 20A, on 2000VA model only)


Selected output voltage -15% to +10%
"2 Hz / sec
nominal ±10% / ±2% selectable
<1° typical (max.7° during tracking frequency range)
1

36 , 36 , 72 , 72
3/7 , 3/9 , 6/7 , 6/9
Sealed lead acid , maintenance free
up to 6 years (depending on use)
1.5 A
3 hours for 90% capacity, std battery

 

12 , 12 , 11 , 12

35/16 , 37/17 , 64/29 , 71/32
3.4x17.2x18.5 inch , 3.4x17.2x21.3 inch
87x438x470 mm , 87x438x540 mm
steel-plastic / IP20

UL 1778, 4th Edition
EN 62040-2
32 to 104°F (o to +40°C)
< 45 dB(A), load and temperature dependent
95% (non-condensing)

1. Due to continuous product improvements, program specifications are subject to change without notice.

bottom of page