GE SG Series UPS
Delivering Best-in-Class Efficiency with eBoost Technology. The GE Energy SG Series is one of the most efficient and reliable Three Phase UPS Systems, providing best-in-class output performance and critical power protection for your data center needs.The SG Series UPS solutions are designed and optimized to provide high efficiency at partial load conditions. The SG Series UPS assures low input current harmonic distortion and best-in-class output voltage regulation and dynamic response. This helps customers save operational costs while implementing environmentally-friendly solutions.
Features & Benefits
• Up to 99% operating efficiency with written efficiency guarantees
• eBoost operation minimizes efficiency losses providing annual power & cooling savings up to $300k for 5MW data center
• eBoost line conditioning & voltage regulation via Bypass Inductor patented design
• Innovative product technologies that boost efficiency, reliability and lengthen battery life
• Top or bottom cable access
• Matching battery and maintenance bypass cabinet for easy configuration
• Front Maintainability Design reduces mean time to repair (MTTR)
• Scalable Solution
• Redundant Parallel Architecture (RPA) provides reliability, redundancy and scalability
• Parallel up to 6 UPS Modules
• Long history of experience with Redundant Parallel Architecture (RPA) which increases system reliability by eliminating single point of failures
Technical Specifications (10-150kVA)
TOPOLOGY
TECHNOLOGY
OPERATING MODES
OUTPUT POWER RATING kVA
Output Power Factor
Dimensions W x D x H (inches)
Weight w/o Batteries (lbs)
Noise Level dB(A)
Input Voltage (VAC)
Input Voltage Range
Input Frequency
Input Power Factor
Output Voltage (sinusoidal) (VAC)
Output Frequency
Output THD at Linear Load
Output THD at Non-linear Load
Crest Factor
Overload Capability on Inverter
Overload Capability on Automatic Bypass
OUTPUT VOLTAGE REGULATION
100% Load
50% Load
Ambient Operating Temp.
Color
Classifications and Listing
RFI and Surge Protection
Standard Connectivity
Warranty
True on-line, double conversion (VFI) with integral static switch and internal maintenance bypass
Advanced IGBT with SVM strategy, microprocessor controlled at optimal switching frequency
True on-line double conversion, automatic bypass, frequency converter, RPA™ up to eight (8) units
10*
.8
27 x 32 x 71
735
60
20*
.8
27 x 32 x 71
736
60
30
.8
27 x 32 x 71
970
60
40
.8
27 x 32 x 71
1147
60
50
.8
27 x 32 x 71
1257
60
80
.8
32 x 32 x 71
1489
63
100
.8
32 x 32 x 71
1929
65
120
.8
47 x 32 x 71
2006
65
150
.8
47 x 32 x 71
2160
65
480V, 3 Phase, 4 Wire w/ground (grounded WYE)
-20% to +15% (without battery discharge)
60Hz +/-10%
.8 PF (.93 with input filter) (.93 with 5th filter)
480V, 3 Phase, 4 Wire w/ground
60Hz +/-10%
<2%
<3%
3:1
<2%
<3%
3:1
<2%
<3%
3:1
<2%
<3%
3:1
<2%
<3%
3:1
<2%
<3%
3:1
<2%
<3%
3:1
<2%
<3%
3:1
<2%
<3%
3:1
125% @ 10 min., 150% @ 1 min.
200% @ 5 min., 110% continuously
90.0
89.5
89.0
88.7
91.0
90.5
91.0
90.5
91.8
92.2
92.0
92.5
92.4
92.9
92.7
93.1
92.8
93.3
32°-104°F (0°- 40°C)
RAL 9003 (white)
UL 1778 / IP20 / NEMA-PE-1 / ISO9001
EN 50091-2 / IEC 62040-2 / IEEE 587 B / FCC Class A compliance **
RS-232; programmable alarm contacts; programmable relays, SNMP (optional)
Twelve (12) months after commissioning or eighteen (18) months after shipment, whichever occurs first ***
1. Due to continuous product improvements, program specifications are subject to change without notice.
* Units available with internal batteries
** FCC Feature available as option
*** Extended Warranties available
Technical Specifications (225-300kVA)
TOPOLOGY
TECHNOLOGY
OPERATING MODES
OUTPUT POWER RATING kVA
Output Power Factor
Output Power Rating (kW)
Dimensions W x D x H (inches)
Weight w/o Batteries (lbs)
Noise Level dB(A)
Input Voltage (VAC)
Input Voltage Range
Input Frequency
Input Power Factor
Output Voltage (sinusoidal) (VAC)
Output Frequency
Output THD at Linear Load
Output THD at Non-linear Load
Crest Factor
Overload Capability on Inverter
Overload Capability on Automatic Bypass
OUTPUT VOLTAGE REGULATION
Static
0-100% Step Load
100% Load
50% Load
Ambient Operating Temp.
Color
Classifications and Listing
RFI and Surge Protection
Standard Connectivity
Warranty
True on-line, double conversion (VFI) with integral static switch and internal maintenance bypass
Advanced IGBT with SVM strategy, microprocessor controlled at optimal switching frequency
True on-line double conversion, automatic bypass, frequency converter, RPA™ up to eight (8) units
225
.8
180
65 x 32 x 71
2756
67
225
.8
180
65 x 32 x 71
2756
67
225
.8
180
65 x 32 x 71
2756
67
225
.8
180
65 x 32 x 71
2756
67
300
.8
240
65 x 32 x 71
3087
67
300
.8
240
65 x 32 x 71
3087
67
300
.8
240
65 x 32 x 71
3087
67
300
.8
240
65 x 32 x 71
3087
67
480V, 3 Phase, 4 Wire w/ground (grounded WYE)
-20% to +15% (without battery discharge)
60Hz +/-10%
.8 PF (.93 with input filter)
480V, 3 Phase, 4 Wire w/ground
60Hz +/-10%
<2%
<3% (IEC 62040)
>3:1
<2%
<3% (IEC 62040)
>3:1
<2%
<3% (IEC 62040)
>3:1
<2%
<3% (IEC 62040)
>3:1
<2%
<3% (IEC 62040)
>3:1
<2%
<3% (IEC 62040)
>3:1
<2%
<3% (IEC 62040)
>3:1
<2%
<3% (IEC 62040)
>3:1
125% @ 10 min., 150% @ 1 min.
200% @ 5 min., 110% continuously
+/- 1%
+/- 3%
92.4
92.7
+/- 1%
+/- 3%
92.4
92.7
+/- 1%
+/- 3%
92.4
92.7
+/- 1%
+/- 3%
92.4
92.7
+/- 1%
+/- 3%
92.7
93.1
+/- 1%
+/- 3%
92.7
93.1
+/- 1%
+/- 3%
92.7
93.1
+/- 1%
+/- 3%
92.7
93.1
32°-104°F (0°- 40°C)
RAL 9003 (white)
UL 1778 / IP20 / NEMA-PE-1 / ISO9001
EN 50091-2 / IEC 62040-2 / IEEE 587 B / FCC Class A compliance *
RS-232; programmable alarm contacts; programmable relays, SNMP (optional)
Twelve (12) months after commissioning or eighteen (18) months after shipment, whichever occurs first **
1. Due to continuous product improvements, program specifications are subject to change without notice.
* FCC Feature available as option.
** Extended Warranties available.
Technical Specifications (750kVA)
RECTIFIER CONFIGURATION
POWER RATING
Output Capacity
POWER FACTOR
Output Power Factor
ENERGY EFFICIENCY
-50% Load
-100% Load
Heat Rejection (btu/hr)
PHYSICAL
Weight w/o batteries (lbs / kg)
Dimensions ( WxDxH) inches (mm)
INPUT
Input Voltage
Voltage Range
Frequency
Input THD
Input THD
OUTPUT
Output Voltage
Frequency
Crest Factor
Voltage Regulation
Static
100% Step Load
Voltage Distortion
100% Linear Load
100% Non-Linear Load
Overload Capability
Inverter
Bypass
BATTERY
Compatibility
Float Voltage
Recharge Time
GENERAL
Audible Noise
Operating Temperature
Humidity
Safety Classifications & Listings
Enclosure
Communication / Connectivity
Color
Warranty
6-PULSE (5TH FILTER
750kVA / 675kW
0.9
94.2%
93.5%
161,435
9,557 / 4,335
6-PULSE (5TH & 11TH FILTER)
750kVA / 675kW
0.9
94.1%
93.4%
162,897
9,696 / 4,398
12-PULSE (W/O FILTER)
750kVA / 675kW
0.9
92.1%
91.8%
207,100
11,091 / 5,031
12-PULSE (11TH FILTER)
750kVA / 675kW
0.9
92.0%
91.7%
208,634
11,230 / 5,094
146.5 x 35.4 x 76.7 (3,720 x 900 x 1,950) inverter & rectifier cabinets
480 V, 3-phase, 4-wire w/ground (3-wire available)
-15% to +10% (w/o battery discharge)
60 Hz +/- 5%
<7%
0.93 lagging
480 V, 3-phase, 4-wire w/ground
3:1
+/- 1%
+/- 3%
2% THD maximum
3% THD maximum
60 Hz +/- 5%
<5%
0.96 lagging
480 V, 3-phase, 4-wire w/ground
93.4%
3:1
+/- 1%
+/- 3%
2% THD maximum
3% THD maximum
60 Hz +/- 5%
<9%
0.82 lagging
480 V, 3-phase, 4-wire w/ground
3:1
+/- 1%
+/- 3%
2% THD maximum
3% THD maximum
60 Hz +/- 5%
<4%
0.86 lagging
480 V, 3-phase, 4-wire w/ground
3:1
+/- 1%
+/- 3%
2% THD maximum
3% THD maximum
60 Hz +/- 0.01% free running — 60 Hz +/- 4% synchronized with utility
25% for 10 minutes; 150% for 30 seconds
110% continuous; 200% for 5 minutes
VRLA or Wet cell
545 VDC @ 68° F (20° C)
10x discharge time (for battery runtime = 30 minutes)
75 db(A) at 5 feet
UPS: 32° to 104° F (0° - 40° C); Battery: 68° to 77° F (20° - 25° C)
0-95%; non-condensing
UL 1778 / IEC62040 / ISO 9001
IP20 and NEMA-PE-1
RS-232; programmable alarm contacts; programmable relays; SNMP (optional)
White (RAL 9003)
12 months from start-up